BEKA 4/20mA Loop Powered Intrinsically Safe Panel Indicator – BA307E

BA307EThese BEKA fourth generation intrinsically safe 4/20mA loop powered indicators have large high contrast displays with a very wide viewing angle.

Operating over an extended temperature range they contain many standard features previously only available as options.

Coated printed circuit boards plus extensive thermal and vibration testing provides maximum reliability supported by a three year guarantee.

      • ATEX & IECEx gas & dust intrinsic safety certification, optional INMETRO
      • FM & cFM gas intrinsic safety certification
      • IP66 Front panel
      • -40°C to +70°C operation
      • Internal calibrator
      • Root extractor and lineariser
      • Tare function
      • Optional: Backlight – may be loop or separately powered / Alarms

Specification:
Mounting & Enclosure Panel: 96mm x 48mm
Protection: Front IP66, rear IP20
Display: 4 digits 15mm high
Certification:
Gas – Group II Category 1G Ex ia IIC T5 Ga – 40°C ≤ Ta ≤ +70°C
Dust – Group II Category 1D Ex ia IIIC T80°C Da IP20 -40°C ≤ Ta ≤ +70°C